Titan PPM Series (3P/3P) – Tower
MODEL
GENERAL
UPS Type | Tower |
Phase | 3 phase in / 3 phase out |
Cabinet Capacity* | 90KW |
One Power Module Capacity | 30KVA / 30KW |
Max. Power Module Capacity | 3 |
Max. Battery Set No.** | 3 |
Dimension (mm) | 1100 x 600 x 1475 (D x W x H) |
Weight (kgs) | 675 |
INPUT
Connection Type | Terminal |
Nominal Voltage | 3 x 380VAC / 400VAC / 415VAC (3Ph+N) |
Voltage Range | 305 ~ 478 VAC at 100% load
208 ~ 304VAC at <70% load |
Frequency Range | 40Hz ~70Hz |
Power Factor | > 0.99 at 100% load
>0.98 at 50% load |
THDi | < 3% @ 100% load |
OUTPUT
Connection Type | Terminal |
Nominal Voltage | 3 x 380VAC / 400VAC / 415VAC (3Ph+N) |
Voltage Regulation (Steady state) | ≦ ± 1% Typical (balanced load)
≦ ± 2% Typical (unbalanced load) |
Frequency Range (Synchronized) | 46~54Hz or 56~64Hz |
Overload Capability | 1 hour for 110%
10 mins for 125% 1 min for 150% and 200ms for >150% |
Efficiency | Up to 94.5% |
Harmonic Distortion | ≦ 2% THD (Linear Load)
≦ 4% THD (Non-linear Load) |
CONNECTIVITY, CONTROL & MONITORING
Front panel | Status LED, Function keys, LCD display |
Communication | Smart RS232*
USB Port Emergency Power Off (EPO) |
BATTERY
TYPE | Built-in Battery |
Nominal Voltage | +/- 216V (12V x 36 Pcs) |
Maximum Voltage | +/- 240V (12V x 40 Pcs) |
Minimum Voltage | +/- 192V (12V x 32 Pcs) |
Maximum Charging Current (Per Power Module) | 8A |
GENERAL
UPS Type | Tower |
Phase | 3 phase in / 3 phase out |
Cabinet Capacity* | 120KW |
One Power Module Capacity | 30KVA / 30KW |
Max. Power Module Capacity | 4 |
Max. Battery Set No.** | 5 |
Dimension (mm) | 1100 x 600 x 2010 (D x W x H) |
Weight (kgs) | 932 |
INPUT
Connection Type | Terminal |
Nominal Voltage | 3 x 380VAC / 400VAC / 415VAC (3Ph+N) |
Voltage Range | 305 ~ 478 VAC at 100% load
208 ~ 304VAC at <70% load |
Frequency Range | 40Hz ~70Hz |
Power Factor | > 0.99 at 100% load
>0.98 at 50% load |
THDi | < 3% @ 100% load |
OUTPUT
Connection Type | Terminal |
Nominal Voltage | 3 x 380VAC / 400VAC / 415VAC (3Ph+N) |
Voltage Regulation (Steady state) | ≦ ± 1% Typical (balanced load)
≦ ± 2% Typical (unbalanced load) |
Frequency Range (Synchronized) | 46~54Hz or 56~64Hz |
Overload Capability | 1 hour for 110%
10 mins for 125% 1 min for 150% and 200ms for >150% |
Efficiency | Up to 94.5% |
Harmonic Distortion | ≦ 2% THD (Linear Load)
≦ 4% THD (Non-linear Load) |
CONNECTIVITY, CONTROL & MONITORING
Front panel | Status LED, Function keys, LCD display |
Communication | Smart RS232*
USB Port Emergency Power Off (EPO) |
BATTERY
TYPE | Built-in Battery |
Nominal Voltage | +/- 216V (12V x 36 Pcs) |
Maximum Voltage | +/- 240V (12V x 40 Pcs) |
Minimum Voltage | +/- 192V (12V x 32 Pcs) |
Maximum Charging Current (Per Power Module) | 8A |
GENERAL
UPS Type | Tower |
Phase | 3 phase in / 3 phase out |
Cabinet Capacity* | 120 KW or 80 KW |
One Power Module Capacity | 30KVA / 30KW or 20KVA / 20KW |
Max. Power Module Capacity | 4 |
Max. Battery Set No.** | – |
Dimension (mm) | 1100 x 600 x 1475 (D x W x H) |
Weight (kgs) | 335 or 333 |
INPUT
Connection Type | Terminal |
Nominal Voltage | 3 x 380VAC / 400VAC / 415VAC (3Ph+N) |
Voltage Range | 305 ~ 478 VAC at 100% load
208 ~ 304VAC at <70% load |
Frequency Range | 40Hz ~70Hz |
Power Factor | > 0.99 at 100% load
>0.98 at 50% load |
THDi | < 3% @ 100% load |
OUTPUT
Connection Type | Terminal |
Nominal Voltage | 3 x 380VAC / 400VAC / 415VAC (3Ph+N) |
Voltage Regulation (Steady state) | ≦ ± 1% Typical (balanced load)
≦ ± 2% Typical (unbalanced load) |
Frequency Range (Synchronized) | 46~54Hz or 56~64Hz |
Overload Capability | 1 hour for 110%
10 mins for 125% 1 min for 150% and 200ms for >150% |
Efficiency | Up to 94.5% |
Harmonic Distortion | ≦ 2% THD (Linear Load)
≦ 4% THD (Non-linear Load) |
CONNECTIVITY, CONTROL & MONITORING
Front panel | Status LED, Function keys, LCD display |
Communication | Smart RS232*
USB Port Emergency Power Off (EPO) |
BATTERY
TYPE | Built-in Battery |
Nominal Voltage | +/- 216V (12V x 36 Pcs) |
Maximum Voltage | +/- 240V (12V x 40 Pcs) |
Minimum Voltage | +/- 192V (12V x 32 Pcs) |
Maximum Charging Current (Per Power Module) | 8A for 30KW power module
6A for 20KW power module |
GENERAL
UPS Type | Tower |
Phase | 3 phase in / 3 phase out |
Cabinet Capacity* | 180 KW or 120 KW |
One Power Module Capacity | 30KVA / 30KW or 20KVA / 20KW |
Max. Power Module Capacity | 6 |
Max. Battery Set No.** | – |
Dimension (mm) | 1100 x 600 x 1475 (D x W x H) |
Weight (kgs) | 437.5 or 434.5 |
INPUT
Connection Type | Terminal |
Nominal Voltage | 3 x 380VAC / 400VAC / 415VAC (3Ph+N) |
Voltage Range | 305 ~ 478 VAC at 100% load
208 ~ 304VAC at <70% load |
Frequency Range | 40Hz ~70Hz |
Power Factor | > 0.99 at 100% load
>0.98 at 50% load |
THDi | < 3% @ 100% load |
OUTPUT
Connection Type | Terminal |
Nominal Voltage | 3 x 380VAC / 400VAC / 415VAC (3Ph+N) |
Voltage Regulation (Steady state) | ≦ ± 1% Typical (balanced load)
≦ ± 2% Typical (unbalanced load) |
Frequency Range (Synchronized) | 46~54Hz or 56~64Hz |
Overload Capability | 1 hour for 110%
10 mins for 125% 1 min for 150% and 200ms for >150% |
Efficiency | Up to 94.5% |
Harmonic Distortion | ≦ 2% THD (Linear Load)
≦ 4% THD (Non-linear Load) |
CONNECTIVITY, CONTROL & MONITORING
Front panel | Status LED, Function keys, LCD display |
Communication | Smart RS232*
USB Port Emergency Power Off (EPO) |
BATTERY
TYPE | External Battery |
Nominal Voltage | +/- 216V (12V x 36 Pcs) |
Maximum Voltage | +/- 240V (12V x 40 Pcs) |
Minimum Voltage | +/- 192V (12V x 32 Pcs) |
Maximum Charging Current (Per Power Module) | 8A for 30KW power module
6A for 20KW power module |
GENERAL
UPS Type | Tower |
Phase | 3 phase in / 3 phase out |
Cabinet Capacity* | 200KW |
One Power Module Capacity | 20KW |
Max. Power Module Capacity | 10 |
Max. Battery Set No.** | – |
Dimension (mm) | 1100 x 600 x 1475 (D x W x H) |
Weight (kgs) | 611 |
INPUT
Connection Type | Terminal |
Nominal Voltage | 3 x 380VAC / 400VAC / 415VAC (3Ph+N) |
Voltage Range | 305 ~ 478 VAC at 100% load
208 ~ 304VAC at <70% load |
Frequency Range | 40Hz ~70Hz |
Power Factor | > 0.99 at 100% load
>0.98 at 50% load |
THDi | < 3% @ 100% load |
OUTPUT
Connection Type | Terminal |
Nominal Voltage | 3 x 380VAC / 400VAC / 415VAC (3Ph+N) |
Voltage Regulation (Steady state) | ≦ ± 1% Typical (balanced load)
≦ ± 2% Typical (unbalanced load) |
Frequency Range (Synchronized) | 46~54Hz or 56~64Hz |
Overload Capability | 1 hour for 110%
10 mins for 125% 1 min for 150% and 200ms for >150% |
Efficiency | Up to 94.5% |
Harmonic Distortion | ≦ 2% THD (Linear Load)
≦ 4% THD (Non-linear Load) |
CONNECTIVITY, CONTROL & MONITORING
Front panel | Status LED, Function keys, LCD display |
Communication | Smart RS232*
USB Port Emergency Power Off (EPO) |
BATTERY
TYPE | External Battery |
Nominal Voltage | +/- 216V (12V x 36 Pcs) |
Maximum Voltage | +/- 240V (12V x 40 Pcs) |
Minimum Voltage | +/- 192V (12V x 32 Pcs) |
Maximum Charging Current (Per Power Module) | 6A |
GENERAL
UPS Type | Tower |
Phase | 3 phase in / 3 phase out |
Cabinet Capacity* | 210KW |
One Power Module Capacity | 30KVA / 30KW |
Max. Power Module Capacity | 8 |
Max. Battery Set No.** | – |
Dimension (mm) | 1100 x 600 x 2010 (D x W x H) |
Weight (kgs) | 549 |
INPUT
Connection Type | Terminal |
Nominal Voltage | 3 x 380VAC / 400VAC / 415VAC (3Ph+N) |
Voltage Range | 305 ~ 478 VAC at 100% load
208 ~ 304VAC at <70% load |
Frequency Range | 40Hz ~70Hz |
Power Factor | > 0.99 at 100% load
>0.98 at 50% load |
THDi | < 3% @ 100% load |
OUTPUT
Connection Type | Terminal |
Nominal Voltage | 3 x 380VAC / 400VAC / 415VAC (3Ph+N) |
Voltage Regulation (Steady state) | ≦ ± 1% Typical (balanced load)
≦ ± 2% Typical (unbalanced load) |
Frequency Range (Synchronized) | 46~54Hz or 56~64Hz |
Overload Capability | 1 hour for 110%
10 mins for 125% 1 min for 150% and 200ms for >150% |
Efficiency | Up to 94.5% |
Harmonic Distortion | ≦ 2% THD (Linear Load)
≦ 4% THD (Non-linear Load) |
CONNECTIVITY, CONTROL & MONITORING
Front panel | Status LED, Function keys, LCD display |
Communication | Smart RS232*
USB Port Emergency Power Off (EPO) |
BATTERY
TYPE | External Battery |
Nominal Voltage | +/- 216V (12V x 36 Pcs) |
Maximum Voltage | +/- 240V (12V x 40 Pcs) |
Minimum Voltage | +/- 192V (12V x 32 Pcs) |
Maximum Charging Current (Per Power Module) | 8A |
GENERAL
UPS Type | Tower |
Phase | 3 phase in / 3 phase out |
Cabinet Capacity* | 300KW |
One Power Module Capacity | 30KVA / 30KW |
Max. Power Module Capacity | 10 |
Max. Battery Set No.** | – |
Dimension (mm) | 1100 x 600 x 2010 (D x W x H) |
Weight (kgs) | 620 |
INPUT
Connection Type | Terminal |
Nominal Voltage | 3 x 380VAC / 400VAC / 415VAC (3Ph+N) |
Voltage Range | 305 ~ 478 VAC at 100% load
208 ~ 304VAC at <70% load |
Frequency Range | 40Hz ~70Hz |
Power Factor | > 0.99 at 100% load
>0.98 at 50% load |
THDi | < 3% @ 100% load |
OUTPUT
Connection Type | Terminal |
Nominal Voltage | 3 x 380VAC / 400VAC / 415VAC (3Ph+N) |
Voltage Regulation (Steady state) | ≦ ± 1% Typical (balanced load)
≦ ± 2% Typical (unbalanced load) |
Frequency Range (Synchronized) | 46~54Hz or 56~64Hz |
Overload Capability | 1 hour for 110%
10 mins for 125% 1 min for 150% and 200ms for >150% |
Efficiency | Up to 94.5% |
Harmonic Distortion | ≦ 2% THD (Linear Load)
≦ 4% THD (Non-linear Load) |
CONNECTIVITY, CONTROL & MONITORING
Front panel | Status LED, Function keys, LCD display |
Communication | Smart RS232*
USB Port Emergency Power Off (EPO) |
BATTERY
TYPE | External Battery |
Nominal Voltage | +/- 216V (12V x 36 Pcs) |
Maximum Voltage | +/- 240V (12V x 40 Pcs) |
Minimum Voltage | +/- 192V (12V x 32 Pcs) |
Maximum Charging Current (Per Power Module) | 8A |