The rugged design incorporates an impeller flow sensor and two temperature probes.
- Cost savings over other systems offered on the market today
- The temperature probe is conveniently mounted directly in the flow sensor tee
- Commissioning of this meter can be completed in the field via a computer connection
-
Electrical InputPower 12…35V DC, 12…28V AC
Communication Modbus RTU, BACnet MST -
Electrical OutputScaled Pulse Open drain, 0.01…100 Hz max.
-
MaterialsHousing: Polycarbonate
Flow Sensor: PEEK
Potting Material: Polyurethane
Tee Material: Brass -
Sensor Body SizesTee Sizes 3/4 in., 1 in., 1-1/4 in., 1-1/2 and 2 in.
-
EnvironmentalFluid Temperature –6.7…126.7 °C
Ambient Temperature –20…65 °C -
Accuracy± 2% of flow rate within the flow range
± 0.5% repeatability
RTD meets IEC751 Class B
-
Flow Range1…15 ft/sec
-
Flow Range
Diameter 380 BTU Meter Flow Range 0.75 in. (19 mm) 1.65…24.69 gpm (6…93 lpm) 1 in. (25 mm) 2.70…40.48 gpm (10…153 lpm) 1.25 in. (32 mm) 4.66…69.93 gpm (17…265 lpm) 1.5 in. (38 mm) 6.35…95.18 gpm (24…360 lpm) 2 in. (50 mm) 10.49…157.34 gpm (40…595 lpm)